Copy Future-proof OT-data center

Stadt St.Gallen, Stadtwerke

Key facts

Canton / Country
St.Gallen · St. Gallen
Contract type
Services
Project
42084
Client
Stadt St.Gallen, Stadtwerke
Published
12 Sept 2026
Offers due by
15 Jan 2027, 16:00

Description

Delivery, installation, and commissioning of six regulating transformers: OS 110kV, US switchable from 10kV to 20kV, with an apparent power of 40MVA (ONAN) and 50MVA (ONAF). The OS and US windings are rated for a continuous load of 50MVA. Operation without active cooling is permitted up to 40MVA; above 40MVA, the regulating transformer must automatically engage forced cooling.


Intended Use

Regulating transformer with compensating winding


Operating Mode

Continuous Operation


Design

Power transformer with tap changer on the primary side, switchable from 10kV to 20kV undervoltage


Construction

Oil-filled transformer with air passages on the OS and US sides for outdoor or indoor installations, and road-transportable for delivery


Expected Service Life

60 years

Accessing documents and participating may require signing in to simap.ch.

This is not an official publication. The data published on www.simap.ch is authoritative. simap.ch