Building 07B / SKP 225.4 Fire Compartmentation
Spitalanlagengesellschaft HOCH Health Ostschweiz
Key facts
- Canton / Country
- St. Gallen
- Contract type
- Construction
- Project
- 44172
- Client
- Spitalanlagengesellschaft HOCH Health Ostschweiz
- Published
- 21 Sept 2026
- Offers due by
- 3 Nov 2026, 23:59
Description
Fire-stopping systems for horizontal and vertical wall and ceiling penetrations, whether concealed or exposed. Applications cover openings for electrical cables, ventilation ducts, and plumbing, heating, and gas piping—including rectangular and circular shapes or larger surface areas. Fire-stopping ratings of EI (S) 90 apply to concrete slabs and shafts, as well as sand-lime brick walls, concrete walls, and lightweight partition walls. Installation involves either a system using 50–60 mm mineral fiber boards coated on both sides with a fire-retardant finish, or a rigid seal using special mortar. All fire-stopping systems must be constructed to be smoke- and gas-tight.
Accessing documents and participating may require signing in to simap.ch.
This is not an official publication. The data published on www.simap.ch is authoritative. simap.ch